Non Directional Overcurrent Protection - '7sr110 Argus'
Product Brochure
Model Name/Number | 7SR110 ARGUS |
Relay Type | REYROLLE - NON-DIRECTIONAL OVERCURRENT PROTECTION |
Brand | Siemens |
Usage/Application | TO PROVIDE THE MAIN PROTECTION ON FEEDERS & INTERCONNECTORS & THE BACKUP PROTECTION ON PLANT ITEMS. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | OVERCURRENT RELAY |
Reyrolle 7SR110
The 7SR11 series of relays provide overcurrent and earth fault protection. These relays are typically applied to provide the main protection on feeders and interconnectors and the backup protection on items of plant such as transformers. On distribution system circuits overcurrent and earth fault protection are often the only protection installed.
Features
The relay functionality allows highly flexible settings for current and time grading making it compatible with all types of overcurrent protection.
The relays are available in single and four pole variants housed in E4 cases with the IEC 61850 protocol option housed in an E6 case. Integrated logic is provided to allow the optimal configuration of relay functionality with the relays analogue inputs and binary input/output circuits.
Protection, instrumentation and metering functionality is accessible via data comms channel(s). A front USB port for local PC connection or rear electrical RS485 port for remote connection is provided.
Cold load settings
Four settings groups
Password protection - 2 levels
User programmable logic
Self-monitoring
Circuit breaker trip counter and timer
Fault, event and waveform records
Functions
Protection functions
Undercurrent (37)
Broken conductor (46BC)
Negative phase sequence overcurrent (46NPS)
Thermal overload (49)
Overcurrent (50, 51)
Earth fault (50G, 50N, 50SEF, 51G, 51N, 51SEF)
High impedance REF (64H)
Supervision functions
CT supervision (60CTS)
Trip & close circuit supervision (74T/CCS)
Inrush detector (81HBL2)
Circuit breaker Fail (50BF)
Control functions
Auto reclose (79)
Monitoring functions
Primary/secondary current phases and earth
Historical demand record
Positive phase sequence (PPS) current
Negative phase sequence (NPS) current
Non Directional Overcurrent Protection - '7SR210 ARGUS'
Product Brochure
Model Name/Number | 7SR210 ARGUS |
Relay Type | REYROLLE - NON - DIRECTIONAL OVER-CURRENT PROTECTION |
Brand | Siemens |
Usage/Application | TO PROVIDE THE MAIN PROTECTION ON FEEDERS & INTERCONNECTORS & THE BACKUP PROTECTION ON PLANT ITEMS. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | NON-DIRECTIONAL OVER-CURRENT PROTECTION |
Reyrolle 7SR210
The 7SR210 series of relays provide overcurrent and earth fault protection. These relays are typically applied to provide the main protection on feeders and interconnectors and the backup protection on items of plant such as transformers, Relays have four current inputs and are housed in E6 or E8 cases.
Features
Integrated logic is provided to allow the optimal configuration of relay functionality with the relays analogue inputs and binary input/output circuits. The optional auto-reclose feature offers an integrated solution for use on OHL feeders.
The relay functionality allows highly flexible settings for current and time grading making it compatible with all types of overcurrent protection.
Protection, instrumentation and metering functionality is accessible via data comms channel(s). A front USB port for local PC connection and rear electrical RS485 port for remote connection are provided as standard, additional ports are available as options.
Cold load settings
Four settings groups
Password protection - 2 levels
User programmable logic
Self-monitoring
Circuit breaker trip counter and timer
Fault, event and waveform records
Functions
Protection functions
Undercurrent (37)
Broken conductor (46BC)
Negative phase sequence overcurrent (46NPS)
Thermal overload (49)
Overcurrent (50, 51)
Earth fault (50G, 50N, 50SEF, 51G, 51N, 51SEF)
Directional control of overcurrent & earth fault (67)
High impedance REF (64H)
Under/over voltage (27/59)
Negative phase sequence voltage (47)
Voltage controlled overcurrent (51V)
Neutral voltage displacement (59N)
Under/over frequency (81)
Supervision functions
CT supervision (60CTS)
Trip & close circuit supervision (74T/CCS)
VT supervision (60VTS)
Inrush detector (81HBL2)
Circuit breaker fail (50BF)
Control functions
Auto reclose (79)
Monitoring functions
Primary/secondary current phases and earth direction
Primary/secondary line and phase voltages
Apparent power and power factor
Real and reactive power
W Hr & VAr Hr forward and reverse
Historical demand record
Positive phase sequence (PPS) voltage & current
Negative phase sequence (NPS) voltage & current
Zero phase sequence (ZPS) voltage
Directional Over-Current Protection- '7SR224 ARGUS'
Product Brochure
Model Name/Number | REYROLLE - DIRECTIONAL OVERCURRENT PROTECTION - '7SR224 ARGUS' |
Relay Type | REYROLLE - DIRECTIONAL OVERCURRENT PROTECTION |
Brand | Siemens |
Usage/Application | TYPICALLY INSTALLED AS AN INTEGRAL CONTROLLER FOR A POLE MOUNTED RECLOSER. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | DIRECTIONAL OVERCURRENT PROTECTION |
Reyrolle 7SR224
Reyrolle 7SR224 series relays include for directional control of three-phase overcurrent and earth fault functionality and typically installed as an integral controller for a pole mounted recloser. The controller offers an integrated auto-reclose solution for use on OHL feeders.
Features
The relay functionality allows highly flexible settings for current and time grading making it compatible with all types of overcurrent protection.
Relays have four current and four voltage inputs and are housed in E10 cases.
Integrated logic is provided to allow the optimal configuration of relay functionality with the relays analogue inputs and binary input/output circuits.
Protection, instrumentation and metering functionality is accessible via data comms channel(s). A front USB port for local PC connection and rear electrical RS485 port for remote connection are provided as standard, additional ports are available as options.
-
Cold load settings
-
Eight settings groups
-
Password protection - 2 levels
-
User programmable logic
-
Self-monitoring
-
Circuit breaker trip counter and timer
-
Fault, event and waveform records
Functions
Protection functions
-
Undercurrent (37)
-
Broken conductor (46BC)
-
Negative phase sequence overcurrent (46NPS)
-
Thermal overload (49)
-
Overcurrent (50, 51)
-
Earth fault (50G, 50SEF, 51G, 51SEF)
-
High impedance REF (64H)
-
Under/over voltage (27/59)
-
Negative phase sequence voltage (47)
-
Voltage controlled overcurrent (51V)
-
Neutral voltage displacement (59N)
-
Directional control of overcurrent & earth fault (67)
Supervision functions
-
CT supervision (60CTS)
-
Trip & close circuit supervision (74T/CCS)
-
VT supervision (60VTS)
-
Inrush detector (81HBL2)
-
Circuit breaker fail (50BF)
Control functions
-
Auto reclose (79)
Monitoring functions
-
Primary/secondary current phases and earth direction
-
Primary/secondary line and phase voltages
-
Apparent power and power factor
-
Real and reactive power
-
W Hr & VAr Hr forward and reverse
-
Historical demand record
-
Positive phase sequence (PPS) voltage & current
-
Negative phase sequence (NPS) voltage & current
-
Zero phase sequence (ZPS) voltage
Directional Over-Current Protection - '7SR220 Argus'
Product Brochure
Model Name/Number | 7SR220 ARGUS |
Relay Type | REYROLLE - DIRECTIONAL OVERCURRENT PROTECTION |
Brand | Siemens |
Usage/Application | FEEDER PROTECTION FOR DISTRIBUTION & INDUSTRIAL NETWORKS |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | DIRECTIONAL OVER-CURRENT PROTECTION |
Reyrolle 7SR220
7SR220 series relays include for directional control of the overcurrent and earth fault functionality and are typically installed where fault current can flow in either direction i.e. on interconnected systems. Relays have five current and four voltage inputs they are housed in E6 or E8 cases.
Features
Integrated logic is provided to allow the optimal configuration of relay functionality with the relays analogue inputs and binary input/output circuits. The optional auto-reclose feature offers an integrated solution for use on OHL feeders.
The relay functionality allows highly flexible settings for current and time grading making it compatible with all types of overcurrent protection.
Protection, instrumentation and metering functionality is accessible via data comms channel(s). A front USB port for local PC connection and rear electrical RS485 port for remote connection are provided as standard, additional ports are available as options.
-
Cold load settings
-
Four settings groups
-
Password protection - 2 levels
-
User programmable logic
-
Self-monitoring
-
Circuit breaker trip counter and timer
-
Fault, event and waveform records
Functions
Protection functions
-
Undercurrent (37)
-
Broken conductor (46BC)
-
Negative phase sequence overcurrent (46NPS)
-
Thermal overload (49)
-
Overcurrent (50, 51)
-
Earth fault (50G, 50N, 50SEF, 51G, 51N, 51SEF)
-
Directional control of overcurrent & earth fault (67)
-
High impedance REF (64H)
-
Under/over voltage (27/59)
-
Negative phase sequence voltage (47)
-
Voltage controlled overcurrent (51V)
-
Neutral voltage displacement (59N)
-
Under/over frequency (81)
Supervision functions
-
CT supervision (60CTS)
-
Trip & close circuit supervision (74T/CCS)
-
VT supervision (60VTS)
-
Inrush detector (81HBL2)
-
Circuit breaker fail (50BF)
Control Functions
-
Auto reclose (79)
Monitoring functions
-
Primary/secondary current phases and earth direction
-
Primary/secondary line and phase voltages
-
Apparent power and power factor
-
Real and reactive power
-
W Hr & VAr Hr forward and reverse
-
Historical demand record
-
Positive phase sequence (PPS) voltage & current
-
Negative phase sequence (NPS) voltage & current
-
Zero phase sequence (ZPS) voltage
Transformer Differential Protection- '7SR242 DUOBIAS'
Product Brochure
Model Name/Number | 7SR242 DUOBIAS |
Relay Type | REYROLLE - TRANSFORMER DIFFERENTIAL PROTECTION |
Brand | Siemens |
Usage/Application | USED AS A PROTECTION, CONTROL & MONITORING RELAY FOR TWO WINDING TRANSFORMERS OF ALL VECTOR GROUPS. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | TRANSFORMER DIFFERENTIAL PROTECTION |
Reyrolle 7SR242
The 7SR242 is used as a protection, control and monitoring relay for two winding transformers of all vector groups, primary configurations/connections and earthing connections.
Features
The relay functionality also allows its application in auto-transformer and reactor protection schemes.
Relays are housed in size E8 or E10 cases. Integrated logic is provided to allow the optimal configuration of relay functionality with the relays analogue inputs and binary input/output circuits.
Protection, control, instrumentation and metering functionality is accessible via data comms channel(s). A front USB port for local PC connection or rear electrical RS485 port for remote connection is provided. Additional rear port options are available.
-
Cold load settings
-
Eight settings groups
-
Password protection - 2 levels
-
User programmable logic
-
Self-monitoring
-
Circuit breaker trip counters
-
Fault, event and waveform records
Functions
Protection functions
-
Over-fluxing (24)
-
Under/over-voltage (27/59)
-
Undercurrent (37)
-
Negative phase sequence overcurrent (46NPS)
-
Thermal overload (49)
-
Overcurrent (50, 51)
-
Earth fault (50G, 50N, 51G, 51N)
-
Neutral voltage displacement (59N)
-
High impedance REF (64H)
-
Biased differential (87BD)
-
High-set differential (87HS)
Supervision functions
-
Circuit breaker Fail (50BF)
-
Trip circuit supervision (74TC)
-
Inrush detector (81HBL2)
-
Over-fluxing detector (81HBL5)
Monitoring functions
-
Primary/secondary currents phases and earth direction
-
Relay operate and restraint currents
-
Positive phase sequence (PPS) current
-
Negative phase sequence (NPS) current
-
Zero phase sequence (ZPS) current
-
Thermal status
-
Primary/secondary single phase voltage
-
Frequency and fluxing
-
Historical demand record
Siemens 7SR1004 Overcurrent And Feeder Protection
Product Brochure
Model Name/Number | 7SR1004 |
Brand | Siemens |
Voltage | 220 V |
Usage/Application | Industrial |
Coil Type | Latching |
Number Of Poles | 2 Pole |
Contact Form | DPDT |
Reyrolle 7SR1004 Overcurrent Relay: The Reyrolle 7SR10 Argus overcurrent and earth fault relay is a numerical overcurrent protection relay intended as a low-cost solution for distribution and industrial applications. The Reyrolle 7SR10 Argus overcurrent and earth fault relay is developed using the latest generation of hardware technology and is available in multiple variants depending on the power supply, Binary input/binary output configuration, and data communication facility. Housed in a 4U high, size 4 non-draw-out case and these relays provide protection, monitoring, instrumentation, and metering with integrated input and output logic, data logging, and fault reports. Communication access to the relay functionality is via a front USB port for local PC connection or rear electrical RS485 (optional) port for remote connection.
It has a Universal power supply suitable for both AC and DC.
1A and 5A CT are selectable at the site. Basic communication protocols like MODBUS RTU and IEC 103 are available and they are also site selectable. Relay is equipped with a sufficient number of DI/DO i.e. up to 6 DI and 6 DO.
7SR1003 is designed for current-based protection and 7SR1004 is available with additional voltage inputs to take care of voltage-based protections. 7SR1005 is designed for motor protection applications.
Siemens Reyrolle 7SR1004 Numerical Relay Technical Details:
Current Inputs: 4
Voltage Inputs : 3
Binary Inputs: 9
Binary Outputs: 6
LEDs: 10
Four overcurrent elements are provided in the 7SR1004 relay. 50-1, 50-2, (50-3 & 50-4 – 7SR1004) Each overcurrent element (50-n) has independent settings. 50-n Setting for pick-up current and 50-n Delay follower time delay. The instantaneous elements have a transient free operation. Where directional elements are present the direction of operation can be set using 50-n Dir. Control setting. Directional logic is provided independently for each 50-n element, e.g. giving the option of using two elements set to forward and two elements set to reverse.
Four under/over frequency elements are provided in the 7SR1004 relay. The relay utilizes fundamental voltage measurement values for this function. The frequency calculation is based on the highest input voltage derived from the voltage selection algorithm. The relay utilizes fundamental frequency RMS voltage for this function. All under/over frequency elements have a common setting to measure phase to phase (Ph-Ph) or phase to neutral (Ph-N) voltage using the Frequency Input mode setting. Frequency elements are blocked if all phase voltages fall below the 81 U/V Guard setting. The sense of the element (under-frequency or over-frequency) is set by the 81-n Operation setting.
PROTECTION FUNCTIONS
Broken Conductor, Load Unbalance (46BC)
Negative Phase Sequence Overcurrent (46NPS)
Thermal Overload (49)
Instantaneous Overcurrent Protection (50)
Instantaneous Earth Fault (50N/G)
Time-Delayed Overcurrent Protection (51)
Time-Delayed Derived/Measured Earth Fault Protection (51N/G)
Cold Load Pickup (51C)
Circuit Breaker Fail (50BF)
Time-Delayed Sensitive Earth Fault Protection (51SEF)
Inrush Restraint (81HBL2)
Instantaneous Sensitive Earth Fault (50SEF)
SUPERVISION FUNCTIONS
Trip Circuit Supervision (74TC)
Total Harmonic Distortion Supervision (81THD)
CONTROL FUNCTIONS
Lockout (86)
CB Control
Siemens 7SR1003 Overcurrent And Feeder Protection
Product Brochure
Model Name/Number | 7SR1003 |
Brand | Siemens |
Voltage | 220 V |
Usage/Application | Industrial |
Coil Type | Latching |
Number Of Poles | 2 Pole |
Contact Form | DPDT |
Reyrolle 7SR1003 Overcurrent Relay: The Reyrolle 7SR10 Argus overcurrent and earth fault relay is a numerical overcurrent protection relay intended as a low-cost solution for distribution and industrial applications. The Reyrolle 7SR10 Argus overcurrent and earth fault relay is developed using the latest generation of hardware technology and is available in multiple variants depending on the power supply, Binary input/binary output configuration, and data communication facility. Housed in a 4U high, size 4 non-draw-out case and these relays provide protection, monitoring, instrumentation, and metering with integrated input and output logic, data logging, and fault reports. Communication access to the relay functionality is via a front USB port for local PC connection or rear electrical RS485 (optional) port for remote connection.
It has a Universal power supply suitable for both AC and DC.
1A and 5A CT are selectable at the site. Basic communication protocols like MODBUS RTU and IEC 103 are available and they are also site selectable. Relay is equipped with a sufficient number of DI/DO i.e. up to 6 DI and 6 DO.
7SR1003 is designed for current-based protection and 7SR1004 is available with additional voltage inputs to take care of voltage-based protections. 7SR1005 is designed for motor protection applications.
7SR1003: Current based Protection Relay
Argus Non-directional overcurrent relay
Size 4 molded casing,
4 CT, 10 LEDs, 6 binary inputs/ 6 binary outputs
Measuring input: 1/5A, 50/60 Hz
Auxiliary voltage: 60 to 240 V AC/DC,
binary input tresh. 44 V AC/DC
Standard version – no cover
Communication: Front port: USB and rear: RS485 supporting IEC 60870-5-103 or Modbus RTU or DNP 3.0
Front fascia: w. breaker control pushbuttons
Protection function: a standard version
REYROLLE 7SR1003 PROTECTION FUNCTIONS
Broken Conductor, Load Unbalance (46BC)
Negative Phase Sequence Overcurrent (46NPS)
Thermal Overload (49)
Instantaneous Overcurrent Protection (50)
Instantaneous Earth Fault (50N/G)
Time-Delayed Overcurrent Protection (51)
Time-Delayed Derived/Measured Earth Fault Protection (51N/G)
Cold Load Pickup (51C)
Circuit Breaker Fail (50BF)
Time-Delayed Sensitive Earth Fault Protection (51SEF)
Inrush Restraint (81HBL2)
Instantaneous Sensitive Earth Fault (50SEF)
SUPERVISION FUNCTIONS
Trip Circuit Supervision (74TC)
Total Harmonic Distortion Supervision (81THD)
CONTROL FUNCTIONS
Lockout (86)
CB Control
The comprehensive range of Reyrolle products provides the total protection requirements of distribution markets and industrial applications – ranging from overcurrent protection via transformer protection and voltage control to a full spectrum of auxiliary and trip relays. The portfolio includes many famous products such as “Argus, “Duobias”, “Solkor”, “Rho, etc. Through successive generations, Reyrolle numerical products have been developed to increase value to system operators. Discover the portfolio!
Line Differential Protection - '7SR18 SOLKAR'
Product Brochure
Model Name/Number | 7SR18 SOLKAR |
Relay Type | REYROLLE - LINE DIFFERENTIAL PROTECTION |
Brand | Siemens |
Usage/Application | TO DETECT IN ZONE PHASE & EARTH FAULTS. APPLICABLE TO OVERHEAD LINES & UNDERGROUND CABLE CIRCUITS |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | LINE DIFFERENTIAL PROTECTION |
Reyrolle 7SR18
Our differential protection relay, Reyrolle7SR18, is a numeric three phase differential protection relay used to detect in zone phase and earth faults. This differential protection relay is applied to the overhead line and underground cable circuits as well as shorter circuits such as interconnectors.
Features
Reyrolle 7SR18 differential protection relays have integral back-up overcurrent/earth fault protection and intertripping channels.
Protection Relays (and associated CTs) are installed at each end of the protected circuit. The relays are connected together with a fully supervised fibre optic protection communications link.
Relays have four current inputs and are housed in E6 cases.
Integrated logic is provided to allow the optimal configuration of relay protection functionality with the relay's analogue inputs and binary input/output circuits.
Protection and instrumentation functionality is accessible via the data comms channel - a front USB, RS485 and IEC 61850 (optional) rear ports.
CT ratio correction
Four setting groups
Password protection
Self-monitoring
Circuit breaker trip counter
Fault, event and waveform records
Functions
Protection functions
3-phase, phase segregated current differential protection
Overcurrent
Earth Fault
Supervision functions
Protection comms link supervision
Circuit Breaker Fail
CT Supervision
Trip Circuit Supervision
Control functions
Intertripping
Monitoring functions
Primary/Secondary Current Phases and Earth
Historical Demand Record
Capacitor Bank Protection - '7SR191 CAPA'
Product Brochure
Model Name/Number | 7SR191 CAPA |
Relay Type | REYROLLE - CAPACITOR BANK PROTECTION |
Brand | Siemens |
Usage/Application | DESIGNED WITH ALL OF THE NECESSARY FUNCTIONALITY FOR USE ON SHUNT CONNECTED DIST. CAPACITOR BANKS. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | CAPACITOR BANK PROTECTION |
Reyrolle 7SR191
The 7SR191 Capa is a numerical protection relay with a highly comprehensive functional software package.
Features
The market for power capacitors is continually growing due to the expanding power network driven by increased customer demand. Power capacitors improve the performance, quality and efficiency of the system and minimize power loss. The Reyrolle 7SR191 Capa protection relay is designed with all of the necessary functionality for use on shunt connected distribution capacitor banks arranged in all of the common connection configurations:
Single star
Double star
Delta
H configuration
The Reyrolle 7SR191 Capa is a numerical protection device with a highly comprehensive functional software package which includes a range of integral application functions aimed at reducing installation, commissioning, wiring and engineering time.
User selectable hardware configuration to suit different bank arrangements
- 3 pole overcurrent + 1 pole unbalance
- 1 pole overcurrent + 3 pole unbalanceOptional voltage inputs
Re-energisation blocking to prevent CB closing until the bank has self discharged
Overvoltage protection by integration analysis of current
Suitable for use with both internally/externally fused and fuseless capacitors
User programmable characteristics for all inverse voltage, current and thermal curves
Unbalance protection with natural spill compensation
Functions
Protection functions
Fascia programmable
CB control via fascia, binary inputs and communication SCADA system
User definable logic both via Quicklogic equations and a graphical design tool
Multiple setting groups
Measured values
Fault records
Disturbance waveform records
Event records
6 User alarms for LCD text indications
Trip circuit supervision
Close circuit supervision
Virtual input/output
CB operation counts
Demand metering
Harmonic analysis and THD
Undercurrent/Loss of Supply (37)
Phase unbalance (46M)
Negative phase sequence overcurrent (46NPS)
Thermal overload (49)
Instantaneous overcurrent (50)
Instantaneous earth fault (50N)
Circuit breaker fail (50BF)
Time delayed overcurrent (51)
Time delayed derived earth fault (51N)
Overvoltage by current integration (59C)
Capacitor unbalance current (60C)
High impedance REF (87REF)
Under/overvoltage (27/59)
Negative phase sequence voltage (47)
Neutral voltage displacement (59N)
Directional instantaneous overcurrent (67/50)
Directional instantaneous rarth fault (67/50N)
Directional time delayed overcurrent (67/51)
Directional time delayed earth fault (67/51N)
Under/over frequency (81)
Siemens Reyrolle 5 7SR51
Product Brochure
Brand | Siemens |
Voltage | 220 V |
Mounting Type | Wall Mounted |
Type | Current Relay |
Relay Type | APFC Relay |
Model Name/Number | 7SR51 |
Country of Origin | Made in India |
Siemens Reyrolle 5 7SR51 Overcurrent & Feeder Protection numerical Relay
Siemens reyrolle 5 7SR51 Overcurrent & Feeder Protection device includes a wide range of protection functions and IEC 61850 Ethernet communications as standard. To further minimize the product variants the power supply and the binary inputs cover the full operating range with configurable binary input thresholds.
Reyrolle 7SR51 Overcurrent Protection Relay Features
The Reyrolle 5 is designed for the electricity networks of the future with enhanced communications and cybersecurity
while maintaining a user-friendly interface and easy product management.
The Reyrolle 7SR511 overcurrent device includes a wide range of protection functions and IEC 61850 Ethernet communications as standard. To further minimize the product variants the power supply and the binary inputs cover the full operating range with configurable binary input thresholds.
The large LCD, tactile pushbuttons and programmable LEDs provide a user-friendly product interface and the relay element is withdrawable for easy replacement.
Siemens Reyrolle 5 7SR51 Inputs and outputs
4 CT + 8 BI + 6 BO
4 CT + 13 BI + 8 BO
4 CT + 23 BI + 12 BO
4 CT + 38 BI + 18 BO
4 CT + 4 VT + 9 BI + 8 BO
4 CT + 4 VT + 14 BI + 10 BO
4 CT + 4 VT + 19 BI + 12 BO
4 CT + 4 VT + 39 BI + 20 BO
Communication
Standard front USB port (for configuration using Reydisp PC based software tool) rear RS485, 2 x RJ45 electrical ports or optional optical ethernet connections.
Housing
Size 6 or 12 with drawable design. Display Backlit 128 x 128 LCD with text and graphical display capabilities suitable for single line mimic diagrams.
Reyrolle 7SR51 Numerical Relay Functions
Standard functionality
37/ 37G undercurrent protection
46 Negative sequence overcurrent protection
46BC Broken conductor detection
49 Thermal overload protection
50/ 50N/ 50G Instantaneous overcurrent
50AFD Arc flash detection
50BF Circuit-breaker failure protection – 3 pole
50GS Instantaneous sensitive earth fault measured
50SOTF Switch onto fault
51/ 51N/ 51G Time delayed overcurrent
51CL Cold load overcurrent phase
51GS Time delayed sensitive earth fault measured
52 Circuit-breaker control
60CTS CT supervision
74TC/ 74CC Trip-circuit and close-circuit supervision
79 Automatic reclosing
81HB2 Inrush current detection
86 Lockout
87GH Restricted earth fault protection – high impedance
87NL Restricted earth fault protection – low-impedance
Additional functionality – 7SR5111 Directional
21FL Fault locator
21LB Load blinder
25 Synchrocheck – synchronising function
27 Undervoltage protection – 3 phase
32 Power protection
47 Sequence overvoltage protection
51V Voltage dependent overcurrent phase
55 Power factor
59/ 59Vx Overvoltage protection
59N Neutral voltage displacement
60VTS VT supervision
67/ 67N/ 67G Directional overcurrent
78VS Voltage vector shift
81 Frequency protection – “f>” or “f<“
81R Frequency protection “df/dt”
Monitoring functions
Primary, secondary and phase sequence current & voltage
Siemens Reyrolle 5 7SR54
Product Brochure
Brand | Siemens |
Output Type | Digital |
Usage/Application | Industrial |
Number of Inputs | 9 Digits |
Country of Origin | Made in India |
Model Number | 7SR54 |
Siemens Reyrolle 7SR54 relay: 7SR54 Transformer differential protection relay is designed for the electricity networks of the future with enhanced communications and cybersecurity while maintaining a user-friendly interface and easy product management.
The Reyrolle 7SR54 provides protection, control and monitoring for 2 and 3 winding transformers. All transformer vector groups and earthing connections are considered.
The Reyrolle 7SR54 device includes a wide range of protection-functions and IEC 61850 Ethernet communications as standard. To further minimize the product variants the power supply and the binary inputs cover the full operating range with configurable binary input thresholds.
The large LCD, tactile pushbuttons and programmable LEDs’ provide a user-friendly product interface and the relay
element is withdrawable for easy replacement.
Inputs and Outputs
- 8 CT + 16 BI + 8 BO
- 8 CT + 4 VT + 12 BI + 8 BO
- 8 CT + 4 VT + 37 BI + 18 BO
- 12 CT + 24 BI + 10 BO
- 12 CT + 4 VT + 35 BI + 16 BO
Communication
Standard front USB port (for configuration using Reydisp PC based software tool) rear RS485, 2 x RJ45 electrical ports or optional optical ethernet connections.
Housing Size
12 with drawable design.
Display
Backlit 128 x 128 LCD with text and graphical display capabilities suitable for single line mimic diagrams.
Standard Functionality can include
24 Overexcitation protection
27 Undervoltage protection – 3 phase
27Vx Undervoltage protection – Vx
37 Undercurrent protection phase
37G Undercurrent earth fault measured
46 Negative sequence overcurrent protection
46BC Broken conductor detection
47 Sequence overvoltage protection
49 Thermal overload protection
50 Instantaneous overcurrent phase
50BF Circuit-breaker failure protection 3 pole
50G Instantaneous earth fault measured
50N Instantaneous earth fault calculated
51 Time delayed overcurrent phase
51G Time delayed earth fault measured
51N Time delayed earth fault calculated
52 Circuit-breaker control
59 Overvoltage protection 3 phase
59NVD Neutral voltage displacement
59Vx Overvoltage protection Vx
60CTS-I CT supervision current reference
60VTS VT supervision
74CC Close-circuit supervision
74TC Trip-circuit supervision
81 Frequency protection f> or f<
81HB2 Inrush current detection
81HB5 Overfluxing detection 5th harmonic
86 Lockout
87GH Restricted earth fault protection high impedance
87T-BD Transformer differential protection – biased
87T-HS Transformer differential protection – highest
Additional Functionality Requires VT Inputs
21LB Load blinder (7SR5421)
24 Overexcitation protection
27/27Vx Undervoltage protection
47 Sequence overvoltage protection
51V Voltage dependent overcurrent phase (7SR5421)
59/59Vx Overvoltage protection
59N Neutral voltage displacement
60VTS VT supervision
67/67G/67N Directional phase/earth fault (7SR5421)
81 Frequency protection “f>” or “f<“
Siemens Reyrolle 7PG23 High Impedance Protection Relay
Product Brochure
Model Name/Number | 7PG23 |
Brand | Siemens |
Voltage | 220 V |
Usage/Application | Industrial |
Coil Type | Latching |
Country of Origin | Made in India |
The 7PG23 High Impedance Protection unit protection principle ensures sensitive, high speed operation for internal faults and guaranteed stability during external faults. The stability of the scheme depends upon the operate voltage setting being greater than the maximum voltage that can appear across the relay under a through fault condition. To ensure stability a setting calculation is required for every application to select the protection operate voltage and current settings.
A combination of stabilizing resistors, setting resistors and nonlinear voltage limiting resistors may be required to be connected into the high impedance circuit. The software tool simplifies the calculation and specification process and provides a method for recording the data, saving the engineer time. The High Impedance Software tool has been developed as part of the Reyrolle software suite and is free to download from the website.
The 7PG23 electro-mechanical single phase circulating current protection is used to detect earth faults in high impedance protection schemes. The relay is typically applied used in transformer protection schemes. One relay per phase can be applied to detect both phase and earth faults e.g. on reactors and stator windings of large machines.
The relay is a voltage operating device and has a user selectable operate voltage setting. The relay can be used in conjunction with an external shunt setting resistor where a higher operate current is required. An integral non-linear resistor limits over-voltages occurring during system faults. Operation flag indicator. Relays are housed in size E3 cases.
Protection Functions
-
High impedance restricted earth fault
FEATURES
-
One relay per phase can be applied to detect both phase and earth faults e.g. on reactors and stator windings of large machines.
-
The relay is a voltage operating device and has a user selectable operate voltage setting. The relay can be used in conjunction with an external shunt setting resistor where a higher operating current is required. An integral non-linear resistor limits over-voltages occurring during system faults. Operation flag indicator. Relays are housed in size E3 cases.
-
User selectable voltage setting
-
Integral voltage limiting device
-
Operation flag indicator
The comprehensive range of Reyrolle products provides the total protection requirements of distribution markets and industrial applications – ranging from overcurrent protection via transformer protection and voltage control to a full spectrum of auxiliary and trip relays. The portfolio includes many famous products such as “Argus, “Duobias”, “Solkor”, “Rho, etc. Through successive generations, Reyrolle numerical products have been developed to increase value to system operators. Discover the portfolio!
Synchronizing Check - ''7SR157 ARGUS'
Product Brochure
Model Name/Number | 7SR157 ARGUS |
Relay Type | REYROLLE - SYNCHRONIZING CHECK RELAY |
Brand | Siemens |
Usage/Application | CHECK & SYSTEM SYNCHRONIZING RELAY DESIGNED TO CARRY OUT CONTROLLED CLOSING OF A CIRCUIT BREAKER. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | SYNCHRONIZING CHECK RELAY |
Reyrolle 7SR157
The Reyrolle 7SR157 Argus is a combined check and system synchronising relay designed to carry out controlled closing of a circuit breaker using measurements of the line and bus voltages.
Features
The relay will prevent the closure of a circuit breaker if the differences in phase angle, slip frequency or magnitude of the voltage falls outside prescribed limits.
If the parameters are within limits, the relay will issue an output which can be used to close the circuit breaker directly or in conjunction with an auto-reclose scheme.
Housed in a 4U high, size E4 case, the relay provides instrumentation and fault data with integrated input and output logic, data logging and fault reports. Communication access to the relay functionality is via a front USB port for local PC connection or rear electrical RS485 port for remote Connection.
Functions
Monitoring
-
Undervoltage detector (25)
-
Differential-voltage detector (25)
-
Voltage levels (live and dead status) (25)
-
Close-circuit supervision (74)
-
VT Fail (60)
Control
-
Voltage trim (magnitude and phase) (25)
-
System-split detector (25)
-
Check synchronizing (25)
-
Check synchronizing close guard (25)
-
System synchronizing (25)
-
Close on zero synchronizing (25)
-
System-split lockout (25)
-
Synchronizing bypass (25)
High Impedance Protection -'7SR23 DAD'
Product Brochure
Model Name/Number | 7SR23 DAD |
Relay Type | REYROLLE - HIGH IMPEDANCE PROTECTION |
Brand | Siemens |
Usage/Application | USED AS A UNIT PROTECTION TO DETECT PHASE & EARTH FAULTS. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | HIGH IMPEDANCE PROTECTION |
Reyrolle 7SR23
The 7SR23 DAD is a numeric high impedance circulating current relay that has four current inputs, it is used as a unit protection to detect phase and earth faults.
Features
The relay can be applied to busbars, connections, transformers, reactors and motors.
The relay is used in ‘high impedance’ applications in conjunction with external stabilising resistors and non-linear resistors (Metrosils). Standardised external components can be provided in an Epsilon case to facilitate design and installation.
The integral CT supervision feature detects open circuits in the CT secondary wiring circuits, a consideration where CT circuits are switched.
Relays are housed in E6 or E8 cases. Integrated logic is provided to allow the optimal configuration of relay input and output functionality. Protection, instrumentation and metering functionality is accessible via data comms channels. A front fascia USB port for local connection and RS485 rear port for remote connection are provided as standard, additional rear ports are available as options.
Functions
Protection functions
Overall differential protection 87/50(G)
Restricted earth fault protection 87REF
Earth fault (50G)
Supervision functions
CT supervision (CT50)
Fault clearance monitor (87/50BF)
Monitoring functions
Instrumentation
Further functions
IEC 61850 option
Eight settings groups
Password protection
Self monitoring
Fault, event and waveform records
Reyrolle Trip Circuit Supervision Relay - 7PJ13
Product Brochure
Brand | Siemens |
Model Name/Number | 7PJ13 |
Relay Type | Reyrolle - Trip Circuit Supervision |
Usage/Application | USED TO MONITOR AND SUPERVISE THE INTEGRITY OF A CIRCUIT BREAKER'S TRIP COIL & OTHER WIRING CIRCUITS |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | REYROLLE - TRIP CIRCUIT SUPERVISION |
Reyrolle 7PJ13
The 7PJ13 Trip Circuit Supervision Relay is an electronic-circuit based relay. The relay is a member of Siemens Reyrolle protection devices product family. It is used to monitor and supervise the integrity of a circuit-breaker’s trip coil and other wiring circuits of low-voltage and medium-voltage networks.
Features
The 7PJ13 is connected with a circuit-breaker to monitor the trip circuit positions (make or break). The 7PJ13 generates a trip circuit failure alarm, either if the trip circuit supply is disconnected or if the trip circuit connection is changed to an open circuit. Trip circuit continuity is measured by supplying the supervision current of 0.7 mA to 1.5 mA and sensing the flow of current with two optocouplers. The circuit-breaker contact indicates the status of the relay whether the circuit-breaker is in a make position or a break position.
The features of the Trip Circuit Supervision Relay are:
- A universal auxiliary voltage range with very low burden (i.e.)
– AC 24 V to AC 240 V/DC 24 V to DC 240 V
– AC 110 V to AC 240 V/DC 110 V 20 DC 240 V
at less than 4 W. - A universal supervision voltage range (i.e.) DC 24 V to DC 240 V.
- A compact design 96 mm x 48 mm (Width x Height)
- Fitted with flush-mounting
- Continuous supervision of trip circuit in pre-closed, post-closed condition, and latched trip condition.
- Detects faults such as auxiliary voltage loss and circuit breakage in supervised circuits.
- Indicates operational status by a single LED with dual color.
- The relay complies with IEC 60255 standards.
Functions
The trip circuit supervision relay is used in the following field applications:
- The relay is used for monitoring activities. The trip circuit wiring is supervised from the positive supply to the negative supply when the circuit-breaker is in a make position or a break position.
- The relay is used for detecting and generating a circuit-breaker alarm, if the trip circuit supply has failed.
- The relay is used to generate an alarm if the trip signal is received but the circuit breaker fails to operate.
- The binary outputs can be wired on to a numerical protection relay to indicate the faulted circuit to remote SCADA.
Non Directional Overcurrent Protection - '7SR45 ARGUS'
Product Brochure
Model Name/Number | 7SR45 ARGUS |
Relay Type | REYROLLE - NON DIRECTIONAL OVER - CURRENT PROTECTION |
Brand | Siemens |
Usage/Application | PROTECTION FOR RMUs; INCOMERS; FEEDERS & MV/LV TRANSFOMERS INTENDED FOR SECONDARY DISTRIBUTION. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | NON DIRECTIONAL OVER-CURRENT PROTECTION |
Reyrolle 7SR45
The Reyrolle 7SR45 Argus self-powered/dual powered non-directional overcurrent and earth fault relay is developed using the latest generation of hardware technology and is available in multiple variants depending on the current transformer (CT), binary input/binary output, power supply, and communication configuration.
Features
The Reyrolle 7SR45 numeric relay provides both definite time and inverse time overcurrent and earth fault protection functions ensuring sensitivity with a minimum operate setting of 0.2 ⋅ I rated for phase overcurrent protection. The relay is CT powered with an option for connection to an external auxiliary supply to provide additional security and communications port for connecting to SCADA. The compact non draw-out design provides front fascia to the navigation keys, LCD, and front USB port for ease of use
Self-powered / auxiliary powered
10 fault records
100 event records
Password protection
Self-monitoring
Overcurrent protection functions (instantaneous and delayed)
Relay integration via Reydisp Evolution PC Software
Sensitivity of 20% nominal current
Serial interface
Hardware
4 current transformer with 1 A or 5 A Inputs
Up to 4 binary Inputs and 4 binary outputs
2 latched binary outputs, 1 changeover and 1 normally open
1 pulsed output
- 2 case options for mounting in various RMU's
User Interface
16 character x 2 line backlit LCD
Menu navigation keys
- 9 predetermined LED’s for easy use
- Mechanical flag
Front USB interface
Optional rear RS485 communication port
Functions
Protection functions
- 50 Instantaneous overcurrent - phase
- 50G Instantaneous earth fault - measured
- 50N Instantaneous earth fault - calculated
- 51 Time delayed overcurrent - phase
- 51G Time delayed earth fault - measured
- 50LC Line check/switch onto fault (SOTF)
- 51N Time delayed earth fault - calculated
Ancillary functions
- 49T High speed external trip via binary input
- 68 Protection function blocking/Inrush current blocking
- 86 Lockout
Communications
- IEC 60870-5-103
- MODBUS RTU
Overcurrent Protection - '7SR10 ARGUS'
Product Brochure
Model Name/Number | 7SR10 ARGUS |
Relay Type | REYROLLE - OVERCURRENT PROTECTION |
Brand | Siemens |
Usage/Application | SIMPLE PROTECTION SOLUTION FOR DISTRIBUTION & INDUSTRIAL APPLICATIONS. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | OVER-CURRENT & EARTH FAULT PROTECTION |
Reyrolle 7SR10
The Reyrolle 7SR10 Argus overcurrent and earth fault relay is a numerical overcurrent protection relay intended as a simple protection solution for distribution and industrial applications.
Features
The Reyrolle 7SR10 Argus overcurrent and earth fault relay is developed using the latest generation of hardware technology and is available in multiple variants depending on the power supply, binary input/binary output configuration and data communication facility.
Housed in a 4U high, size 4 non-withdrawable case, these relays provide protection, monitoring, instrumentation, and metering with integrated input and output logic, data logging and fault reports. Communication access to the relay functionality is via a front USB port for local PC connection or rear electrical RS485 (optional) port for remote connection.
Cold load pickup (51C)
Two settings groups
Password protection ??? 2 levels
User programmable logic
Self-monitoring
Circuit breaker trip and maintenance counter
Functions
Protection functions
Broken conductor, load unbalance (46BC)
Negative phase sequence overcurrent (46NPS)
Thermal overload (49)
Instantaneous overcurrent protection (50)
Instantaneous earth fault (50N/G)
Time delayed overcurrent protection (51)
Time delayed derived/measured earth fault protection (51N/G)
Cold load pickup (51C)
Circuit breaker fail (50BF)
Time delayed sensitive earth fault protection (51SEF)
Inrush restraint (81HBL2)
Instantaneous sensitive earth fault (50SEF)
Supervision functions
Trip circuit supervision (74TC)
Total harmonic distortion supervision (81THD)
Control functions
Lockout (86)
CB control
Motor Protection - '7SR105 RHO'
Product Brochure
Model Name/Number | 7SR105 RHO |
Relay Type | REYROLLE - MOTOR PROTECTION |
Brand | Siemens |
Usage/Application | INTENDED FOR USE IN THE MOTOR PROTECTION APPLICATIONS. THEREBY, ALLOWS THE SAFE OPERATION OF A MOTOR |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | MOTOR PROTECTION |
Reyrolle 7SR105
Reyrolle 7SR105 Rho motor protection relay is a numerical protection relay intended for use in the motor protection applications. It provides a highly comprehensive functional software package with a range of integral application functions aimed at reducing installation, wiring, and engineering time.
Features
The device is housed in a 4U high, size 4 non-withdrawable case and these relays provide protection, monitoring, instrumentation, and metering with integrated input and output logic, data logging and fault reports. Communication access to the relay functionality is via a front USB port for local PC connection or rear electrical RS485 port for remote connection.
A wide range of measured values can be viewed on the front LCD or remotely via the communications channel. The integrated control feature allows the safe operation of a motor and monitoring its start and stop operations.
-
Optional RTD inputs
-
Cold load settings
-
Two settings groups
-
Password protection
-
Self-monitoring
-
Circuit breaker trip counter
-
Fault, event and waveform records
Functions
Protection functions
-
Stall protection (14)
-
Undercurrent (37)
-
Current unbalance protection (46)
-
Phase reversal (46Ph Rev)
-
Start protection (48/66)
-
Motor thermal overload (49R)
-
Time-overcurrent protection (50/51)
-
Earth fault (50/51G/N)
-
Backspin protection (81B)
-
Temperature inputs (RTD)
Supervision functions
-
Circuit breaker fail (50BF)
-
CT supervision (60CTS)
-
Trip circuit supervision (74T/CCS)
Monitoring functions
-
Instrumentation
Siemens Reyrolle 7SR57 Motor Protection Numerical Relay
Product Brochure
Usage/Application | Industrial |
Voltage | 220 V |
Current | 12 A |
Number Of Poles | 2 Pole |
Frequency | 50 Hz |
Country of Origin | Made in India |
Siemens Reyrolle 7SR57 motor protection relay includes a wide range of protection functions and IEC 61850 Ethernet communications as standard. To further minimize the product variants the power supply and the binary inputs cover the full operating range with configurable binary input thresholds.
Features
The Reyrolle 5 is designed for the electricity networks of the future with enhanced communications and cyber security while maintaining a user-friendly interface and easy product management.
The 7SR57 motor protection devices include a wide range of protection functions and IEC 61850 Ethernet communications as standard. To further minimize the product variants the power supply and the binary inputs cover the full operating range with configurable binary input thresholds.
The large LCD, tactile pushbuttons and programmable LEDs provide a user-friendly product interface and the relay element is withdrawable for easy replacement.
Inputs and outputs
4 CT + 8 BI + 6 BO
4 CT + 13 BI + 8 BO
4 CT + 4 VT + 9 BI + 8 BO
4 CT + 4 VT + 19 BI + 12 BO
Communication
Standard front USB port (for configuration using Reydisp PC based software tool) rear RS485, 2 x RJ45 electrical ports or optional optical ethernet connections.
Housing
Size 6 or 12 with drawable design. Display Backlit 128 x 128 LCD with text and graphical display capabilities suitable for single line mimic diagrams.
Functions
Standard functionality
14 Locked rotor protection
37/37G Undercurrent protection – phase/earth
46BC Broken conductor detection
46PR Phase-rotation reversal
46UB Phase unbalance
48 Starting-time supervision
49R Rotor thermal overload protection
49TS Temperature sensor supervision 11
50/ 50N/ 50G Instantaneous overcurrent
50AFD Arc flash detection
50BCL Break capacity limit
50BF Circuit-breaker failure protection – 3 pole
51/ 51N/ 51G Time delayed overcurrent
52 Circuit-breaker control
60CTS CT supervision
74TC/ 74CC Trip-circuit and close-circuit supervision
79 Automatic reclosing
81B Backspin monitor
81HB2 Inrush current detection
86 Lockout
87GH Restricted earth fault protection – high-impedance
Optional functionality – Siemens Reyrolle 7SR57
27/27Vx Undervoltage protection
32 Power protection
47 Sequence overvoltage protection
55 Power factor
59/ 59Vx Overvoltage protection
59N Neutral voltage displacement
60VTS VT supervision
67/ 67N/ 67G Directional overcurrent
81 Frequency protection – “f>” or “f<“
81R Frequency protection – “df/dt“
Monitoring functions of Siemens 7SR57 numerical relay
Primary, secondary and phase sequence current & voltage
Frequency, power, and energy
Fault data, event and waveform records
Motor start data log
Motor Protection - '7SR17 RHO'
Product Brochure
Model Name/Number | 7SR17 RHO |
Relay Type | REYROLLE - MOTOR PROTECTION |
Brand | Siemens |
Usage/Application | MOTOR PROTECTION DURING ALL STARTING & RUNNING SEQUENCES. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | MOTOR PROTECTION |
Reyrolle 7SR17
The Reyrolle 7SR17 Rho is a numeric protection relay with four current inputs and optionally three voltage inputs. The relay is applied to motors and their connections providing an integrated protection system.
Features
The relay is typically used as a stand-alone device but can be supplied with an external unit to interface with remote temperature detectors embedded in the motor or installed on auxiliary equipment.
The Reyrolle 7SR17 Rho relay includes thermal protection optimised for motor applications and motor starting supervision algorithms. Several other protections are also provided and are selectable as required so that a solution appropriate to the installation can be achieved.
The Reyrolle 7SR17 Rho is housed in an E4 case.
Full user configurability and integrate logic allows the optimal configuration of relay input and output functionality.
-
Optional RTD inputs
-
Cold load settings
-
Eight settings groups
-
Password protection
-
Self-monitoring
-
Circuit breaker trip counter
-
Fault, event and waveform records
Functions
Protection functions
-
Stall protection (14)
-
Under/over voltage (27/59)
-
Power/power factor (32/55)
-
Undercurrent (37)
-
Current unbalance protection (46)
-
Phase reversal (46Ph Rev)
-
Voltage unbalance (47)
-
Start protection (48/66)
-
Motor thermal overload (49R)
-
Directional overcurrent (67)
-
Directional earth fault (67G/67N)
-
Backspin protection (81B)
-
Under/over frequency (81)
-
High impedance REF (87REF)
-
Temperature inputs (via comms port) (RTD)
Supervision functions
-
Circuit breaker fail (50BF)
-
CT supervision (60CTS)
-
VT supervision (60VTS)
-
Trip circuit supervision (74T/CCS)
Monitoring functions
-
Instrumentation
Reyrolle - Linear Fibre Optic Arc Fault Sensor - '7xg3140 - Ra40'
Product Brochure
Brand | Siemens |
Model Name/Number | 7XG3140 - RA40 |
Relay Type | REYROLLE - LINEAR FIBRE OPTIC ARC FAULT SENSOR |
Height | REFER BROCHURE PDF FOR SPECS |
Usage/Application | FAST CLEARANCE OF ARCING FAULTS ON BUSBARS & WITHIN METAL CLAD SWITCHGEAR & ASSOCIATED CABLE BOXES. |
Device Short Name | REYROLLE - LINEAR FIBRE OPTIC ARC FAULT SENSOR |
Reyrolle 7XG31
Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on busbars & within metal clad switchgear & associated cable boxes.
Features
The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. Conventional current based protection techniques are at times challenged by the nature of arcing faults, and can result in slow protection clearance times. Slow protection clearance times increase the risk to nearby personnel and increase the degree of damage to plant and equipment. By employing an optical detection technique, arc fault protection results in fast clearance of arcing faults.
When an arc fault start current is coincident with a signal from the optical sensor a trip command is output. An arc trip only signal can be achieved within 10ms which can be considerably faster than that provided by a traditional IDMT overcurrent relay. This is because the onset of an arcing fault can occur at relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection.
The ReyArc range of protection devices provide multiple arc fault protection schemes depending on your protection system requirements:
ReyArc Arc Protection range:
7XG3120 Arc Fault Monitor Relay, with 2 or 3 arc point sensor inputs, 2 separate tripping- duty outputs.
7XG3123 ARC Fault Interface Module, with 1 or 2 arc point sensor inputs, high-speed binary output to interface with protection relay binary input.
7XG3124 Arc Fault Monitor, with IEC 61850 and up to 16 arc sensor inputs, 2 tripping-duty outputs.
7XG3127 Arc Fault Monitor, with 4 arc point sensor Inputs and 1 linear sensor input, 2 separate tripping zones with 4 output tripping contact and 1 supervision contact.
7XG3130 High-Speed Arc Sensor, with 1 or 2 optical point sensors per unit.
7XG3140 High-Speed Linear Arc Sensor, with optional sensor length up to 40 metres
Function
The 7XG3130 - RA30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the RA30 occurs in a few milli-seconds. When an arc is detected, the resistance presented by the RA30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the 7XG3120 - RA20 and the trip output contacts close. Also, this increased current flow is detected by the 7XG3123 – RA23 module which responds in < 1 ms to close a solid-state contact to activate the arc fault input on the protection relay. The 7XG3127 – RA27 may be configured to suit a wide range of arc flash monitoring applications.
Optical Arc Fault Sensor '7XG3130 - REYARC 30'
Product Brochure
Model Name/Number | 7XG3130 - RA30 |
Relay Type | REYROLLE - OPTICAL ARC FAULT SENSOR |
Brand | Siemens |
Usage/Application | FAST CLEARANCE OF ARCING FAULTS ON BUSBARS & WITHIN METAL CLAD SWITCHGEAR & ASSOCIATED CABLE BOXES. |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | OPTICAL ARC FAULT SENSOR |
Reyrolle 7XG31
Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on busbars & within metal clad switchgear & associated cable boxes.
Features
The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. Conventional current based protection techniques are at times challenged by the nature of arcing faults, and can result in slow protection clearance times. Slow protection clearance times increase the risk to nearby personnel and increase the degree of damage to plant and equipment. By employing an optical detection technique, arc fault protection results in fast clearance of arcing faults.
When an arc fault start current is coincident with a signal from the optical sensor a trip command is output. An arc trip only signal can be achieved within 10ms which can be considerably faster than that provided by a traditional IDMT overcurrent relay. This is because the onset of an arcing fault can occur at relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection.
The ReyArc range of protection devices provide multiple arc fault protection schemes depending on your protection system requirements:
ReyArc Arc Protection range:
7XG3120 Arc Fault Monitor Relay, with 2 or 3 arc point sensor inputs, 2 separate tripping- duty outputs.
7XG3123 ARC Fault Interface Module, with 1 or 2 arc point sensor inputs, high-speed binary output to interface with protection relay binary input.
7XG3124 Arc Fault Monitor, with IEC 61850 and up to 16 arc sensor inputs, 2 tripping-duty outputs.
7XG3127 Arc Fault Monitor, with 4 arc point sensor Inputs and 1 linear sensor input, 2 separate tripping zones with 4 output tripping contact and 1 supervision contact.
7XG3130 High-Speed Arc Sensor, with 1 or 2 optical point sensors per unit.
7XG3140 High-Speed Linear Arc Sensor, with optional sensor length up to 40 metres
Function
The 7XG3130 - RA30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the RA30 occurs in a few milli-seconds. When an arc is detected, the resistance presented by the RA30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the 7XG3120 - RA20 and the trip output contacts close. Also, this increased current flow is detected by the 7XG3123 – RA23 module which responds in < 1 ms to close a solid-state contact to activate the arc fault input on the protection relay. The 7XG3127 – RA27 may be configured to suit a wide range of arc flash monitoring applications.
ARC Fault Interface Module - '7XG3123 - RA23'
Product Brochure
Brand | Siemens |
Relay Type | REYROLLE - ARC FAULT INTERFACE MODULE |
Model Name/Number | 7XG3123 - RA23 |
Dimensions | REFER BROCHURE PDF FOR SPECS |
Device Short Name | ARC FAULT INTERFACE MODULE |
I Deal In | New Only |
Reyrolle 7XG31
Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on busbars & within metal clad switchgear & associated cable boxes.
Features
The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. Conventional current based protection techniques are at times challenged by the nature of arcing faults, and can result in slow protection clearance times. Slow protection clearance times increase the risk to nearby personnel and increase the degree of damage to plant and equipment. By employing an optical detection technique, arc fault protection results in fast clearance of arcing faults.
When an arc fault start current is coincident with a signal from the optical sensor a trip command is output. An arc trip only signal can be achieved within 10ms which can be considerably faster than that provided by a traditional IDMT overcurrent relay. This is because the onset of an arcing fault can occur at relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection.
The ReyArc range of protection devices provide multiple arc fault protection schemes depending on your protection system requirements:
ReyArc Arc Protection range:
7XG3120 Arc Fault Monitor Relay, with 2 or 3 arc point sensor inputs, 2 separate tripping- duty outputs.
7XG3123 ARC Fault Interface Module, with 1 or 2 arc point sensor inputs, high-speed binary output to interface with protection relay binary input.
7XG3124 Arc Fault Monitor, with IEC 61850 and up to 16 arc sensor inputs, 2 tripping-duty outputs.
7XG3127 Arc Fault Monitor, with 4 arc point sensor Inputs and 1 linear sensor input, 2 separate tripping zones with 4 output tripping contact and 1 supervision contact.
7XG3130 High-Speed Arc Sensor, with 1 or 2 optical point sensors per unit.
7XG3140 High-Speed Linear Arc Sensor, with optional sensor length up to 40 metres
Function
The 7XG3130 - RA30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the RA30 occurs in a few milli-seconds. When an arc is detected, the resistance presented by the RA30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the 7XG3120 - RA20 and the trip output contacts close. Also, this increased current flow is detected by the 7XG3123 – RA23 module which responds in < 1 ms to close a solid-state contact to activate the arc fault input on the protection relay. The 7XG3127 – RA27 may be configured to suit a wide range of arc flash monitoring applications.
Voltage & Frequency Protection - '7SR158 ARGUS'
Product Brochure
Model Name/Number | 7SR158 ARGUS |
Relay Type | REYROLLE - VOLTAGE & FREQUENCY PROTECTION |
Brand | Siemens |
Usage/Application | DESIGNED FOR CONNECTION TO VOLTAGE TRANSFORMERS |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | VOLTAGE & FREQUENCY PROTECTION |
Reyrolle 7SR158
The Reyrolle 7SR158 Argus voltage and frequency relays are numerical, multifunctional devices, with functionality designed for connection to voltage transformers.
Features
The voltage and frequency functionality is supplemented by data storage, instrumentation, user configurable logic and data communication features. A menu based user-friendly interface provides local access to relay settings, instruments and operational data. The fascia also benefits from 9 user configurable, tri-coloured LEDs and a USB port for PC access.
The key functions provided include 27/59 -under and overvoltage, 81 -under and over frequency, 78 -Voltage vector shift and 81R -Rate of change of frequency.
Relays have three voltage inputs, six binary inputs and eight binary outputs and are housed in a size E4 case. Programmable logic is provided to allow the optimal configuration of relay functionality. A rear electrical RS485 port is provided for SCADA connection using either IEC60870-5-103, DNP3.0 or MODBUS RTU protocol.
Functions
Protection functions
Under/over voltage
Under/over frequency
Rate of change of frequency
Negative phase sequence voltage
Neutral voltage displacement
Voltage vector shift
Supervision functions
Trip and close circuit supervision
Lockout
Monitoring functions
Primary/secondary line and phase voltages
Historical demand record
Positive phase sequence (PPS) voltage
Negative phase sequence (NPS) voltage
Zero phase sequence (ZPS) voltage
Further functions
Four settings groups
2 levels password protection
Self monitoring
Circuit breaker trip and maintenance counters
Fault, event and waveform records
Programmable user logic
User alarms
Virtual inputs/outputs
Front USB communication port
Rear RS485 communication port
ARC Fault Monitor Relay - '7XG3124 - REYARC 24'
Product Brochure
Model Name/Number | 7XG3124 - RA24 |
Relay Type | REYROLLE - ARC FAULT MONITOR RELAY |
Brand | Siemens |
Usage/Application | FAST CLEARANCE OF ARCING FAULTS ON BUSBARS & WITHIN METAL CLAD SWITCHGEAR & ASSOCIATED CABLE BOXES |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | ARC FAULT MONITOR RELAY |
Reyrolle 7XG31
Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on busbars & within metal clad switchgear & associated cable boxes.
Features
The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. Conventional current based protection techniques are at times challenged by the nature of arcing faults, and can result in slow protection clearance times. Slow protection clearance times increase the risk to nearby personnel and increase the degree of damage to plant and equipment. By employing an optical detection technique, arc fault protection results in fast clearance of arcing faults.
When an arc fault start current is coincident with a signal from the optical sensor a trip command is output. An arc trip only signal can be achieved within 10ms which can be considerably faster than that provided by a traditional IDMT overcurrent relay. This is because the onset of an arcing fault can occur at relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection.
The ReyArc range of protection devices provide multiple arc fault protection schemes depending on your protection system requirements:
ReyArc Arc Protection range:
7XG3120 Arc Fault Monitor Relay, with 2 or 3 arc point sensor inputs, 2 separate tripping- duty outputs.
7XG3123 ARC Fault Interface Module, with 1 or 2 arc point sensor inputs, high-speed binary output to interface with protection relay binary input.
7XG3124 Arc Fault Monitor, with IEC 61850 and up to 16 arc sensor inputs, 2 tripping-duty outputs.
7XG3127 Arc Fault Monitor, with 4 arc point sensor Inputs and 1 linear sensor input, 2 separate tripping zones with 4 output tripping contact and 1 supervision contact.
7XG3130 High-Speed Arc Sensor, with 1 or 2 optical point sensors per unit.
7XG3140 High-Speed Linear Arc Sensor, with optional sensor length up to 40 metres
Function
The 7XG3130 - RA30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the RA30 occurs in a few milli-seconds. When an arc is detected, the resistance presented by the RA30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the 7XG3120 - RA20 and the trip output contacts close. Also, this increased current flow is detected by the 7XG3123 – RA23 module which responds in < 1 ms to close a solid-state contact to activate the arc fault input on the protection relay. The 7XG3127 – RA27 may be configured to suit a wide range of arc flash monitoring applications.
ARC Fault Monitor Relay - '7XG3120 - REYARC 20'
Product Brochure
Model Name/Number | 7XG3120 - RA20 |
Relay Type | REYROLLE - ARC FAULT MONITOR RELAY |
Brand | Siemens |
Usage/Application | FAST CLEARANCE OF ARCING FAULTS ON BUS BARS & WITHIN METAL CLAD SWITCHGEAR & CABLE BOXES |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | ARC FAULT MONITOR RELAY |
Reyrolle 7XG31
Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on busbars & within metal clad switchgear & associated cable boxes.
Features
The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. Conventional current based protection techniques are at times challenged by the nature of arcing faults, and can result in slow protection clearance times. Slow protection clearance times increase the risk to nearby personnel and increase the degree of damage to plant and equipment. By employing an optical detection technique, arc fault protection results in fast clearance of arcing faults.
When an arc fault start current is coincident with a signal from the optical sensor a trip command is output. An arc trip only signal can be achieved within 10ms which can be considerably faster than that provided by a traditional IDMT overcurrent relay. This is because the onset of an arcing fault can occur at relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection.
The ReyArc range of protection devices provide multiple arc fault protection schemes depending on your protection system requirements:
ReyArc Arc Protection range:
7XG3120 Arc Fault Monitor Relay, with 2 or 3 arc point sensor inputs, 2 separate tripping- duty outputs.
7XG3123 ARC Fault Interface Module, with 1 or 2 arc point sensor inputs, high-speed binary output to interface with protection relay binary input.
7XG3124 Arc Fault Monitor, with IEC 61850 and up to 16 arc sensor inputs, 2 tripping-duty outputs.
7XG3127 Arc Fault Monitor, with 4 arc point sensor Inputs and 1 linear sensor input, 2 separate tripping zones with 4 output tripping contact and 1 supervision contact.
7XG3130 High-Speed Arc Sensor, with 1 or 2 optical point sensors per unit.
7XG3140 High-Speed Linear Arc Sensor, with optional sensor length up to 40 metres
Function
The 7XG3130 - RA30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the RA30 occurs in a few milli-seconds. When an arc is detected, the resistance presented by the RA30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the 7XG3120 - RA20 and the trip output contacts close. Also, this increased current flow is detected by the 7XG3123 – RA23 module which responds in < 1 ms to close a solid-state contact to activate the arc fault input on the protection relay. The 7XG3127 – RA27 may be configured to suit a wide range of arc flash monitoring applications.
ARC Fault Monitor With Linear Sensor Input - '7XG3127 - RA27'
Product Brochure
Model Name/Number | 7XG3127 - RA27 |
Relay Type | REYROLLE - ARC FAULT MONITOR WITH LINEAR SENSOR INPUT |
Brand | Siemens |
Usage/Application | FAST CLEARANCE OF ARCING FAULTS ON BUSBARS & WITHIN METAL CLAD SWITCHGEAR & ASSOCIATED CABLE BOXES |
Overall Dimension | REFER BROCHURE PDF FOR SPECS |
Device Short Name | ARC FAULT MONITOR WITH LINEAR SENSOR INPUT |
Reyrolle 7XG31
Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on busbars & within metal clad switchgear & associated cable boxes.
Features
The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. Conventional current based protection techniques are at times challenged by the nature of arcing faults, and can result in slow protection clearance times. Slow protection clearance times increase the risk to nearby personnel and increase the degree of damage to plant and equipment. By employing an optical detection technique, arc fault protection results in fast clearance of arcing faults.
When an arc fault start current is coincident with a signal from the optical sensor a trip command is output. An arc trip only signal can be achieved within 10ms which can be considerably faster than that provided by a traditional IDMT overcurrent relay. This is because the onset of an arcing fault can occur at relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection.
The ReyArc range of protection devices provide multiple arc fault protection schemes depending on your protection system requirements:
ReyArc Arc Protection range:
7XG3120 Arc Fault Monitor Relay, with 2 or 3 arc point sensor inputs, 2 separate tripping- duty outputs.
7XG3123 ARC Fault Interface Module, with 1 or 2 arc point sensor inputs, high-speed binary output to interface with protection relay binary input.
7XG3124 Arc Fault Monitor, with IEC 61850 and up to 16 arc sensor inputs, 2 tripping-duty outputs.
7XG3127 Arc Fault Monitor, with 4 arc point sensor Inputs and 1 linear sensor input, 2 separate tripping zones with 4 output tripping contact and 1 supervision contact.
7XG3130 High-Speed Arc Sensor, with 1 or 2 optical point sensors per unit.
7XG3140 High-Speed Linear Arc Sensor, with optional sensor length up to 40 metres
Function
The 7XG3130 - RA30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the RA30 occurs in a few milli-seconds. When an arc is detected, the resistance presented by the RA30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the 7XG3120 - RA20 and the trip output contacts close. Also, this increased current flow is detected by the 7XG3123 – RA23 module which responds in < 1 ms to close a solid-state contact to activate the arc fault input on the protection relay. The 7XG3127 – RA27 may be configured to suit a wide range of arc flash monitoring applications.